The technology module SITRANS FST070 is an ultrasonic clamp-onflowmeter transmitter for the SIMATIC ET200SP.
The TM SITRANS FST070 flow transmitter can be operateddirectly in the SIMATIC PCS7 or in TIA Portal with the FST070faceplates. SITRANS FST070 offers real-time data processingand the display of all measuring and status data of the Ultrasonicflowmeter.
The TM FST070 can work with all Siemens ultrasonic clamp-onflowmeters. It can be connected to the FS DSL with FSS200clamp-on sensors.
SITRANS FS DSL with FSS200 clamp-on sensors
优势
Easy integration into automation process control as TIA portaland PCS7 (SIMATIC)
Easy selection and integration of flowmeters viaTIA selector
Precast face plates for TIA portal and PCS7
No additional transmitter between automation and clamp-on sensorsrequired
Cost effective integration of clamp-on flowmeters for watertreatments, control rooms with PCS7
SITRANS FST070 ET 200SP technology module cancombined with all other SIMATIC ET200 modules
Fast and trouble-free communication between the flowmeter and thePLC through digital data communication with up to 10 ms updaterate
SITRANS FST070 and ET 200SP have the ATEX Zone 2Class 1 Div 2 approvals. With the barrierSITRANS I300 the flowmeters sensor can be used in ExZone 1/0 Class 1 Div 1 approval
应用
SITRANS FST070 can be used for machine builders, in thechemical industry or water treatments. The meters are suitable formeasuring on liquid, hydrocarbon and gas. With ET 200SP theSITRANS FST070 can be installed decentralized in smallstations, with fast communication to the control room. Thefaceplates for TIA portal and PCS 7 offer the direct fullremote access to the flow meter. The main industries for theSITRANS FST070 transmitter:
Chemical
Pharmaceutical
District Energy
Water and waste water
Oil
Gas
设计
The SITRANS FST070 is designed as ET200 SP module and candirectly installed with other ET200 SP modules. TheFS DSL cable is directly mounted to the ET 200SP baseunit is providing the supply voltage and the data communication.The SITRANS FSS200 clamp-on sensors with FS DSL can beconnected directly to the SITRANS FST070. For sensors in ATEXZone 0 or 1, the SITRANS I300 barrier must be installedbetween FST070 and the FS DSL.
功能
The following key functionalities are available:
Volume flow rate, mass flow, flow velocity, density, temperature,pressure. kinematic viscosity, standard volume flow(hydrocarbon)
Three built-in totalizers which can freely be set for countingvolume flow, mass flow
Two digital inputs
Two digital outputs
Low flow cut-off
Zero point adjustment
Configurable upper and lower alarm and warning limits for allprocess values
Comprehensive status and error reporting
技术规范
SITRANS FST070 | |
---|---|
Measurementof | Volume flowrate, mass flow, flow velocity, density, temperature, pressure.kinematic viscosity, standard volume flow (hydrocarbon) |
Measurementfunctions | |
Totalizer 1 | Volume flow,mass flow, standard volume flow |
Totalizer 2 | Volume flow,mass flow; standard volume flow |
Totalizer 3 | |
Generalinformation | |
Product typedesignation | Technologymodule TM FST070 |
FW updatepossible | Yes |
UsableBaseUnits | BU 20type B1 |
ET 200SP | |
Engineeringwith | STEP 7TIA Portal configurable/integrated as of version V17 or higher STEP 7configurable/integrated as of version V5.6 SP4 and higher PCS 7 V9.1 or higher PROFINET asof GSD version/GSD revision GSDML V2.35 |
Cable | |
Maximum cablelength to FS DSL | 75 m(max. 150 m) |
Supplyvoltage | |
Load voltageL+ | 24 V DC |
Rated value(DC) | 24 V NEC-Class II |
Permissiblerange, lower limit (DC) | 19.2 V |
Permissiblerange, upper limit (DC) | 28.8 V |
Short-circuitprotection | |
Reversepolarity protection | Yes; againstdestruction |
Inputcurrent | |
Currentconsumption, max. | 500 mA |
Powerloss | |
Typical powerloss, max. | 1.7 W |